人妻夜夜爽天天爽爽一区丨18禁黄网站禁片无遮挡观看丨亚洲欧美日韩国产成人一区丨国产亚洲3p无码一区二区丨亚洲www啪成人一区二区

Time: 2024-08-18  韋克威科技

Current Transformer Saturation - Weikewei - Comes with Professional User Manual

The purpose of a current transformer (CT) is to generate an accurate copy of a current waveform, whose amplitude decreases proportionally to the number of turns. Except for entering saturation state, CT is a very reliable and accurate device in most cases.

How does the current transformer saturate?

A current transformer with a given iron core size can only support the maximum magnetic flux density of a given number of iron cores. As long as the magnetic flux density (the iron core magnetic flux generated by the CT primary current) remains below the maximum magnetic flux target value, the change in magnetic flux will generate a ratio current in the secondary circuit.

When the primary current is too high for the magnetic core to handle more flux, the CT will saturate. In a saturated state, the magnetic flux does not change when the primary current changes (because the magnetic core has already carried the maximum magnetic flux). Due to the absence of magnetic flux changes, there is no secondary current flowing. In other words, in a saturated state, all ratio currents are used as excitation currents and no current flows into the load connected to the CT.

Parameters related to saturation

  • Cross section of CT magnetic core: The larger the cross section, the lower the chance of saturation.

  • Quality and type of steel used for manufacturing cores

  • Burden: The external load applied to the CT secondary is called "burden".

Precautions for the application of current transformers

  • The rated primary current of CT should be equal to or greater than the maximum expected current of the relevant circuit breaker or transformer.

  • The maximum secondary current shall not exceed 20 times the rated current of ANSI C-class CT (5A rated CT is 100A).

  • Star connected CTs generate rated CT secondary current on external CT wires, while delta connected CTs generate 1.732 times the secondary current.

  • The highest CT ratio that can be used in a given application can be used to achieve optimal performance. An excessively high CT ratio may cause issues with relay settings.

  • For multi ratio CT, using lower taps will reduce effective accuracy and increase the chance of saturation.

Performance Calculation of Current Transformer

One of the following methods can be used to estimate the performance of a current transformer (CT):

  1. Formula method

  2. Excitation curve method

  3. ANSI standard

Formula method

The formula method uses the basic transformer equation to calculate the effective magnetic flux density of a specific fault current value. Then compare the calculated magnetic flux density with the performance of the steel used in the CT core and determine whether the core will saturate due to the fault current.

Obtaining the cross-sectional area and maximum magnetic flux density of CT magnetic cores is not easy, and this method is only applicable to certain rare situations. This method will not be discussed again.

Excitation method

The excitation curve represents the curve of CT secondary rms voltage relative to rms current during primary open circuit. A reasonable and accurate secondary excitation curve for a given CT can be obtained by opening the primary coil and applying an appropriate frequency of AC voltage to the secondary coil. It is necessary to measure the current flowing into the CT. The relationship curve between the applied root mean square voltage and the root mean square current is approximately a quadratic excitation curve.

Example 1: For a given 50:5 CT, the excitation curve is provided below. The relay connected to the CT should operate at 60A symmetrical primary current. CT internal resistance=0.0332 Ω, lead resistance=1.25 Ω, relay burden=0.5 Ω. Calculate the actual primary current required to trip the relay.

answer:

Rotation speed=50/5=10

Relay operates at 60/10=6A of CT secondary current

When 6A flows in the secondary circuit, the voltage drop Vs can be calculated as

Vs = 6A *(0.0332Ω+1.25Ω+0.5Ω)= 10.7V

At a secondary excitation voltage of 10.7V, the excitation curve below the excitation current Ie is approximately 5A.

Total primary current=(60A+10 * 5A)=110A

Therefore, the relay will only operate when the primary current is 110A instead of the required 60A.

電流互感器勵磁曲線

This can be improved by selecting a higher ratio CT. For example, by selecting a 100:5 CT with an internal resistance of 0.064 Ω and keeping all other parameters constant,

Rotation speed=100/5=20

The relay operates at CT secondary current of 60/20=3A

When 3A flows in the secondary circuit, the voltage drop Vs can be calculated as

Vs = 3A *(0.064Ω+1.25Ω+0.5Ω)= 5.442V

According to the excitation diagram (not shown), the excitation current Ie with a secondary excitation voltage of 10.7V is approximately 0.22A.

Total primary current=(60A+20 * 0.22A)=64.4A

Therefore, if the current is 64.4A, the relay will operate instead of using 50:5 CT, which requires a current of 110A to operate. If a 200:5 CT is used, the starting current of the relay will be 61.6A.

It is very important to use the internal winding resistance of CT in the calculation using the excitation curve method.

Example 2: The excitation curve can be used to determine whether the CT is sufficient to meet a specific relay accuracy level based on the excitation curve. This can be proven with an example. Consider 600:5 C100 CT. Assuming a total load of 0.5 Ω, including CT winding resistance.

Solution: To check if the relay is sufficient, first calculate the secondary voltage at 20 times the rated secondary current.

Vicorv High-Reliability Electronic Components

Find the excitation voltage corresponding to the excitation current of 10A from the excitation curve. The reason for choosing 10A is that 10A is 10% of 100A, while ANSI C current transformers can ensure a ratio error of 10%, up to 20 times the rated secondary current. Therefore, for a secondary current of 100A, a current of up to 10A can flow into the magnetizing impedance, while a current of 90A can flow into the load, and CT can still meet the accuracy requirement of 10%.

According to the excitation curve below, for an excitation current of 10A, the secondary voltage is 90V. Due to 90V being greater than the calculated 50V, CT is sufficient to meet the accuracy requirements of the relay.

電流互感器飽和

ANSI standard

The ANSI C57-13 relay standard is represented by two symbols: letter marking and rated voltage. For example, C50, C100, C400, etc.

These letters represent the following meanings:

C: Can calculate the transformer ratio

T: The transformer ratio must be determined through testing

C-class current transformers (CTs) have fully distributed windings, so the influence of iron core leakage flux on the ratio can be ignored. The C category covers bushing CT, while the T category covers type transformers. For T-class CT, leakage flux cannot be ignored and will affect the ratio. This article only discusses CT in the C category.


tag: 互感器
主站蜘蛛池模板: 国产精品天天看天天狠| 亚洲6080yy久久无码产自国产| 国产成年无码v片在线| 国产福利视频一区二区| 精品久久久久国产免费| 国内精品伊人久久久久妇| 久久午夜夜伦鲁鲁片免费无码影院 | 亚洲а∨天堂男人无码| av天堂久久精品影音先锋| 日本丰满大乳人妻无码苍井空| 亚洲第一在线综合网站| 成在人线aⅴ免费视频| 中文字幕日韩精品无码内射| 中文字幕无码精品亚洲资源网久久 | 国产精品久久久av久久久| 中文字幕被公侵犯的漂亮人妻| 国产精品久久无码一区二区三区网 | 亚洲人成网站日本片| 国产精品无码av天天爽| 国内精品自国内精品66j影院| 噜妇插内射精品| 亚洲成av人片无码迅雷下载| 97久久超碰亚洲视觉盛宴| 无码丰满人妻熟妇区| 99re6在线观看国产精品| 蜜桃视频在线观看免费网址入口| 国产亚洲视频免费播放| 久久午夜夜伦鲁鲁片免费无码影视| 亚洲人妻av伦理| 少妇人妻激情乱人伦| 日韩av一区二区三区免费看| 国产亚洲一卡2卡3卡4卡老狼| 日本三级香港三级乳网址| 少妇厨房愉情理9仑片视频下载| 免费看国产黄线在线观看| 日韩人妻无码一区2区3区里沙| 国产精品久久久久久爽爽爽| 在线高清理伦片a| 日本va欧美va欧美va精品| 成人av一本不卡二卡| 丰满人妻无奈张开双腿av|